GENERAL DATA,Topology VFI double conversion, Nominal output apparent power kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA. Power factor output PF 0 8 lag 0 9 lag,Nominal output active power kW 8 16 24 32 45 54. Overall efficiency at 100 load in VFI mode 90 0 90 0 90 6 90 5 90 2 90 0. Overall efficiency at 100 load in ECO mode 98 0 98 0 99 0 99 0 98 0 98 0. Heat dissipation at 100 load in VFI mode,kW 0 89 1 78 2 49 3 36 4 89 6 00. nominal PF and charged battery, Cooling air 77 F 86 F 25 C 30 C CFM 154 308 431 582 847 1040. Audible noise level dB A 50 55 61 62 65 65,Battery type Valve regulated lead acid VRLA.
UPS 32 F to 104 F 0 C to 40 C,Operating temperature range. Battery 68 F to 77 F 20 C to 25 C recommended, Storage temperature range 13 F to 131 F 25 C to 55 C. Storage time of the battery without recharge at 68 F 20 C Max 6 months. Relative humidity Max 95 non condensing,Max altitude without power derating 3300 ft. Power derating according to IEC 62040 3 5000 ft 95 6500 ft 91 8200 ft 86 9800 ft 82. Protection degree IP 20 IEC 60529 and NEMA PE 1,Safety Standards UL 1778 IEC 62040 ISO 9001. EMC FCC Class A IEC 62040 2 Class A, Electrostatic discharge immunity 4kV contact 8kV air discharge.
Internal protection All live parts shrouded,Enclosure Metal sheet and castors. 10 20 kVA Packaging suitable for handling by forklift. 30 to 60 kVA Cabinet and packaging suitable for handling by forklift. Color RAL 9003 white, 10 20 kVA Minimum distance from the wall 2 inches 5 cm. Installation, 30 to 60 kVA Can be positioned against a wall and floor. Service access Front and top, External cable connections Front Bottom conduit access. Cooling Forced to top by internal blower, Up to 4 units in parallel for redundancy or capacity in RPA.
Paralleling RPA version,configuration optional, Rectifier bridge Three phase over temperature protection. Nominal 3 x 208 N,10 20 kVA 25 to 20,Standard input voltage. 30 40 kVA 20 to 15,50 60 kVA 15 to 10,Input frequency 60 Hz 10. Input power factor 0 98 lag,10 20 kVA 8,Input current distortion THDI. 30 to 60 kVA 10,Output voltage tolerance 1, Battery ripple current Max 5 of the battery capacity Ah expressed in A.
Battery charging characteristic IU DIN 41773 T compensated floating voltage. 10 20 kVA settable in 3 steps,Battery charging current limit. 30 to 60 kVA settable by parameter, Input power data kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA. Nominal input at inverter nominal load,Current A 25 2 50 4 75 1 100 141 170. and charged battery,KVA 9 1 18 1 27 0 36 1 50 9 61 2. kW 8 9 17 8 26 5 35 4 49 9 60 0,Max input power at inverter nominal load and max.
Current A 27 4 54 7 87 3 113 155 183,battery recharge current programmable. KVA 9 9 19 7 31 4 40 5 55 6 65 9,kW 9 7 19 3 30 8 39 7 54 5 64 6. Max battery charging current programmable A 4 8 9 6 4 8 9 6 15 0 15 0 16 0 16 0. Battery boostcharge Yes selectable,with Additional battery charger option. Modifications reserved Page 2 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. Battery type Standard Valve regulated lead acid VRLA. Number of blocks and battery capacity See battery table on page 5 and 6. Float voltage at 20 C 2 x 164 VDC,Min discharge voltage programmable 2 x 118 VDC.
Recharge time 6 to 8 hours,Automatic and manual battery test Standard. Common battery in parallel system Up to 4 units only for 30 to 60 kVA. Battery power data kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA. DC power at full load and nominal PF kW 8 9 17 8 26 5 35 4 49 9 60 0. Max discharge current at 100 load and nominal PF A 38 75 112 150 211 254. Matching battery cabinets See optional feyatures on page 4. Nominal output power at PF 0 6 0 8 lag 0 6 0 9 lag 10 to 40 kVA 50 60 kVA. Nominal output voltage on site programmable 3 x 208V N. Inverter bridge IGBT technology,Output waveform Sine wave. Output voltage tolerance,dynamic at load step 0 100 0 1. recovery time to 1 3 ms,10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA. output voltage THD for 100 linear load,2 2 1 5 1 5 2 2.
output voltage THD for 100 non linear load EN 50091 3. Output voltage tolerance at 100 unbalanced load Ph N 3. Output frequency 60 Hz,Output frequency tolerance,free running 0 1. with mains synchronisation adjustable to 4,Phase displacement. at 100 balanced load 120 1,at 100 unbalanced load 120 2. Overload capability at nominal PF 125 10 minutes 150 1 minute. Electronic short circuit protection current limit to 2 2 times. Short circuit characteristic,In for 100 ms,10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA. Nominal output current at full load,28A 56A 83A 111A 139A 167A.
Crest factor 3 1,Common input Rectifier Bypass,Input connection. Dual input optional,Thyristors SSM Static Switch module. Electromechanical contactors backfeed protection on. Primary components,bypass and inverter,2 manual switches for maintenance bypass. Voltage limits for inverter bypass load transfers 15. 200 for 2 Minutes,Overload on bypass,2000 for 1 2 cycle non repetitive. INTERFACING, 4 Utility failure General alarm Stop operation load on.
Potential free contacts utility,28 user settable signals. Serial channel RS232 on Delta 9 pin connector Standard. EPO Emergency Power Off Standard,EMERGENCY POWER OFF n c contact customer supplied. Extended Customer Interface Card optional 6 potential free alarm contacts. 2 auxiliary contacts one default configured as Genset. Note all indicated values are typical Variations may be found from one unit to another. Modifications reserved Page 3 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. FRONT PANEL CONTROLS SIGNALS AND ALARMS,LP 33U Series 10 20 kVA. LP 33U Series 30 40 50 60 kVA, The control panel positioned on the UPS front door acts as the UPS user interface and comprises of the following elements.
Back lit Graphic Display LCD with the following characteristics. Multilanguage communication interface, English German Italian Spanish French Finnish Polish Portuguese Czech Slovakian Chinese Swedish Russian and. Graphic diagram indicating UPS status,Command keys and parameters setting. UPS status control LED,OPTIONS UPS internally mounted. COMMUNICATION,1 Extended Customer Interface Card,1 Advanced SNMP Card. 2 RPA Redundant Parallel Architecture to parallel up to 4 units. 2 GE Power Diagnostics, 3 Dual utility input one for rectifier one for bypass.
3 GE Data Protection, 4 EMC filter for dual input only for 30 40 50 60 kVA. 4 Modbus RTU Interface,5 Additional battery charger only for 10 20 kVA. OPTIONS IN ADDITIONAL CABINETS,1 Battery cabinet for 30 to 60 kVA. H Dimensions WxDxH Weight empty,16 93 x 28 55 x 70 95 188 lbs. 430 x 725 x 1802 mm 85 Kg,Modifications reserved Page 4 8.
TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. TECHNICAL DATA,LP 33U Series 10 20 kVA,LP 33U Series 10 20 kVA WEIGHT. UPS without battery UPS with battery,rating UPS floor UPS with UPS with Floor UPS with. loading st shipping battery loading standard shipping. 180 Kg 408 Kg m2 195 Kg 290 395 Kg 657 895 Kg m2 305 410Kg. 397 lbs 84 lbs sq ft 430 lbs 640 871 lbs 135 184 lbs sq ft 673 905lbs. 195 Kg 442 Kg m2 210 Kg 410 Kg 24 Ah 929 Kg m2 24 Ah 425 Kg 24 Ah. 430 lbs 91 lbs sq ft 464 lbs 905 lbs 24 Ah 191 lbs sq ft 24 Ah 938 lbs 24 Ah. Battery 12 Ah Battery 24 Ah 2 x 12 Ah,LP 33U Series 10 20 kVA BATTERY TABLE. UPS rating Battery Autonomy,capacity time,12 Ah 9 min. 10 kVA Mounted inside the UPS cabinet see Weight table. 24 Ah 2 x 12 Ah 26 min, 20 kVA 24 Ah 2 x 12 Ah 9 min Mounted inside the UPS cabinet see Weight table.
Battery autonomy time at 100 load and PF 0 8 lag only with High Rate Battery. Modifications reserved Page 5 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. LP 33U Series 30 40 kVA,29 61 23 63,752mm 16 93 600mm. LP 33U Series 30 40 kVA WEIGHT,UPS without battery UPS with battery. rating UPS floor UPS with Floor UPS with,UPS UPS with battery. loading st shipping loading stand shipping,33 Ah 605 Kg 816 Kg m 630 Kg.
24 blocks 1335 lbs 168 lbs sq ft 1390 lbs, 350 Kg 472 Kg m 375 Kg 33 Ah 860 Kg 1160 Kg m 885 Kg. 772 lbs 97 lbs sq ft 827 lbs 48 blocks 1897 lbs 238 lbs sq ft 1952 lbs. 50 Ah 735 Kg 991 Kg m 760 Kg,24 blocks 1621 lbs 203 lbs sq ft 1676 lbs. 33 Ah 625 Kg 843 Kg m 650 Kg,24 blocks 1379 lbs 173 lbs sq ft 1434 lbs. 370 Kg 499 Kg m 395 Kg 33 Ah 880 Kg 1186 Kg m 905 Kg. 816 lbs 103 lbs sq ft 871 lbs 48 blocks 1941 lbs 243 lbs sq ft 1996 lbs. 50 Ah 755 Kg 1018 Kg m 780 Kg,24 blocks 1665 lbs 209 lbs sq ft 1720 lbs. LP 33U Series 30 40 kVA BATTERY TABLE,Battery capacity Autonomy time Cabinet L.
33 Ah 24 blocks 9 minutes UPS 1 Battery cabinet 40 55 1030mm. 2 x 33 Ah 48 blocks 23 minutes UPS 1 Battery cabinet 40 55 1030mm. 30 kVA 50 Ah 24 blocks 14 minutes UPS 1 Battery cabinet 40 55 1030mm. 4 x 33 Ah 96 blocks 52 minutes UPS 2 Battery cabinets 57 48 1460mm. 2 x 50 Ah 48 blocks 37 minutes UPS 2 Battery cabinets 40 55 1030mm. 33 Ah 24 blocks 6 minutes UPS 1 Battery cabinet 40 55 1030mm. 2 x 33 Ah 48 blocks 14 minutes UPS 1 Battery cabinet 40 55 1030mm. 40 kVA 50 Ah 24 blocks 10 minutes UPS 1 Battery cabinet 40 55 1030mm. 4 x 33 Ah 96 blocks 37 minutes UPS 2 Battery cabinets 57 48 1460mm. 2 x 50 Ah 48 blocks 26 minutes UPS 2 Battery cabinets 57 48 1460mm. Battery autonomy time at 100 load and PF 0 8 lag only with High Rate Battery. Modifications reserved Page 6 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. LP 33U Series 50 60 kVA,S 1 UPS dim,29 61 28 35,752mm 16 93 720mm. LP 33U Series 50 60 kVA WEIGHT STANDARD UPS,UPS without battery UPS with battery. rating UPS floor UPS with Floor UPS with,UPS UPS with battery. loading st shipping loading stand shipping, 50 kVA 460 Kg 532 Kg m2 490 Kg 33 Ah 970 Kg 1122 Kg m2 1000 Kg.
60 kVA 1015 lbs 109 lbs sq ft 1081 lbs 48 blocks 2139 lbs 230 lbs sq ft 2205 lbs. LP 33U Series 50 60 kVA WEIGHT SINGLE ADDITIONAL BATTERY CABINET. Battery capacity Weight Floor loading, 50 kVA 2 x 33 Ah 48 blocks 595 Kg 1312 lbs 1909 Kg m2 391 lbs sq ft. 60 kVA 50 Ah 24 blocks 470 Kg 1037 lbs 1508 Kg m2 309 lbs sq ft. LP 33U Series 50 60 kVA BATTERY TABLE,Battery capacity Autonomy time Cabinet L. 2 x 33 Ah 48 blocks 9 minutes UPS 1 Battery cabinet 45 28 1150mm. 4 x 33 Ah 96 blocks 24 minutes UPS 2 Battery cabinet 62 21 1580mm. 50 kVA 2 x 50 Ah 48 blocks 16 minutes UPS 2 Battery cabinet 62 21 1580mm. 3 x 50 Ah 72 blocks 29 minutes UPS 3 Battery cabinet 79 14 2010mm. 4 x 50 Ah 96 blocks 36 minutes UPS 4 Battery cabinets 96 07 2440mm. 2 x 33 Ah 48 blocks 8 minutes UPS 1 Battery cabinet 45 28 1150mm. 4 x 33 Ah 96 blocks 18 minutes UPS 2 Battery cabinet 62 21 1580mm. 60 kVA 2 x 50 Ah 48 blocks 13 minutes UPS 2 Battery cabinet 62 21 1580mm. 3 x 50 Ah 72 blocks 23 minutes UPS 3 Battery cabinet 79 14 2010mm. 4 x 50 Ah 96 blocks 33 minutes UPS 4 Battery cabinet 96 07 2440mm. Battery autonomy time at 100 load and PF 0 9 lag only with High Rate Battery. Modifications reserved Page 7 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. UPS BLOCK DIAGRAM AND PROTECTIONS,Common input Rectifier Bypass. Dual input Rectifier Bypass optional, Note for all over current protections and wires sizing please to refer to the Installation Guide.
IMPORTANT NOTE,The UPS is designed for TN System, The input neutral shall be grounded at source and shall never be disconnected. 4 pole breaker shall not be used at the UPS input see also IEC 60634 IEC 61140 IEC 61557. Modifications reserved Page 8 8, TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA. Modifications reserved Page 2 8 TDS LPS 33U 10K 60K 1US V020 doc Technical Data Sheets LP 33U Series 10 20 30 40 50 60 kVA GENERAL DATA Topology VFI double conversion Nominal output apparent power kVA 10 kVA 20 kVA 30 kVA 40 kVA 50 kVA 60 kVA Power factor output PF 0 8 lag 0 9 lag